Experiment 4: 2 sofas; 8' x 12' padding; 8' x 12' carpet

Circuit # Circuit Type Cord/Cable Type Trip Type Time to Trip
1 Conventional 18-2, SPT-1 Magnetic 217.3 s
2 AFCI 18-2, SPT-1 Magnetic 209.5 s
3 GFCI 18-2, SPT-1 Magnetic 211.2 s
4 Conventional 16-3 SJTW Magnetic 233.8 s
5 AFCI 16-3 SJTW Magnetic 234.6 s
6 GFCI 16-3 SJTW Magnetic 235.1 s
7 Conventional 12-2 NM Magnetic 227.5 s
8 AFCI 12-2 NM Ground Fault 225.8 s
9 GFCI 12-2 NM Ground Fault 218.3 s
10 Conventional 12-3 NM Magnetic 223.7 s
11 AFCI 12-3 NM Magnetic 227.1 s
12 GFCI 12-3 NM Ground Fault 218.1 s
13 Conventional 18-3 SVT Magnetic 214.3 s
14 AFCI 18-3 SVT Magnetic 216.3 s
15 GFCI 18-3 SVT Magnetic 214.9 s
16 Conventional NISPT-2 Magnetic 218.1 s